Additionally, you must determine the size of
the Area (A) of the opening through which the air is flowing. For
example, the inlet on a suction duct/hose, open area of a funnel or hood, or the
opening in the air discharge of the blower, if measuring discharge air flow.
A. Determine the Area (A) of the opening
and convert it to square feet (sq.ft.).
1. Area for Square or Rectangular openings: Area (A) = Height x Width
A. Determine the area of the opening by measuring the Height and Width in
inches and multiplying them
(HxW) to get Area.
B. Convert the opening size to square feet by dividing the Area by 144.
(144 is the area of 1 square foot in inches)
Example:
A. Height 10" x Width 12" = (10 x 12)=120 square inches.
B. Convert the opening area to square feet: 120" / 144 = 0.8333 sq.ft., round
to 0.84 sq.ft.
2. Area for Circular openings such as duct:
Area (A)=Pi x R2 . (Pi=3.1416)
A. Measure the diameter of the opening in inches to get (D) diameter.
B. Divide diameter by 2 to get Radius (D / 2 = R)
C. Multiply R times itself, to square it, (R x R = R2).
D. Multiply R2 times 3.1416 to get area (A) in square inches.
E. Convert the opening size to square feet by dividing the area by 144.
Example:
A. D = 8"
B. R= (8/2) = 4"
C. R2= (4 x 4) = 16
D. Area = R2 x 3.1416 (16 x 3.1416) = 50.26 square inches. Round off to 50.25
sq.in.
E. Convert area square inches to area square feet: 50.25 / 144 = 0.348. Round
off to 0.35 sq.ft. total area.
B. Determine air velocity through opening.
1. Set the meter to readout in Feet per Minute
(FPM) according to the instrument instructions.
2. Place the instrument into the air flow, at the face of the opening, so it is
reading the representative air flow through the opening and let the meter
reading stabilize. Record the FPM reading. (See Note 2 below for large area
openings.)
C. Calculate Air Flow in Cubic Feet per
Minute
1. Multiply the Area (A) determined from your measurements times the
recorded velocity in FPM to get the approximate CFM.
CFM Example: (Assume a reading of 360 FPM was read on the meter.)
a. Area 0.84 sq.ft x 360 FPM = 302.4 CFM
or
b. Area 0.35 sq. ft. x 360 FPM = 126 CFM
Notes
1. The methods explained here will result in an approximate CFM, not an exact
CFM flow rate. This is due to variables in air flow, turbulence, meter
accuracy, and methodology.
2. For large area openings take several readings at different points on the
face of the opening, record each reading. When a representative sample of
readings has been recorded, average them and use the Average Reading as the
FPM flow rate, not the highest or lowest.